Catalog Number |
Rated Current |
Poles |
Terminal Type |
Torque and Wire Range |
Wire Type |
Base Temp. Rating |
Snap to Release |
Indication |
Optional Cover Catalog No.* |
|
30A |
1 |
Screw |
2.8N-m (25in-lbs) 10-22AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
|
30A |
2 |
Screw |
2.8N-m (25in-lbs) 10-22AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
|
30A |
3 |
Screw |
2.8N-m (25in-lbs) 10-22AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
30A |
1 |
Pressure Plate |
2.8N-m (25in-lbs) 10-14AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
|
30A |
2 |
Pressure Plate |
2.8N-m (25in-lbs) 10-14AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
|
30A |
3 |
Pressure Plate |
2.8N-m (25in-lbs) 10-14AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
30A |
1 |
Box Lug |
2.8N-m (25in-lbs) 6-14AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
|
30A |
2 |
Box Lug |
2.8N-m (25in-lbs) 6-14AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
|
30A |
3 |
Box Lug |
2.8N-m (25in-lbs) 6-14AWG |
CU Only, Solid or Stranded |
130°C |
• |
• |
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
60A |
1 |
Box Lug |
5.6N-m (50in-lbs) 2-4AWG 2.8N-m (25in-lbs) 6-14AWG |
CU-AL, Solid or Stranded |
130°C |
• |
• |
|
|
60A |
2 |
Box Lug |
5.6N-m (50in-lbs) 2-4AWG 2.8N-m (25in-lbs) 6-14AWG |
CU-AL, Solid or Stranded |
130°C |
• |
• |
|
|
60A |
3 |
Box Lug |
5.6N-m (50in-lbs) 2-4AWG 2.8N-m (25in-lbs) 6-14AWG |
CU-AL, Solid or Stranded |
130°C |
• |
• |
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
100A |
1 |
Box Lug |
13.6N-m (120in-lbs) 2/0-6AWG 4.5N-m (40in-lbs) 8AWG 4.0 N-m (35 in-lbs) 10-14AWG |
CU-AL, Solid or Stranded |
130°C |
— |
• |
|
|
100A |
3 |
Box Lug |
13.6N-m (120in-lbs) 2/0-6AWG 4.5N-m (40in-lbs) 8AWG 4.0 N-m (35 in-lbs) 10-14AWG |
CU-AL, Solid or Stranded |
130°C |
— |
• |
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
200A |
1 |
Box Lug |
31.1N-m (275in-lbs) 250kcmil-6 |
CU-AL, Solid or Stranded |
130°C |
— |
— |
— |
|
200A |
3 |
Box Lug |
31.1N-m (275in-lbs) 250kcmil-6 |
CU-AL, Solid or Stranded |
130°C |
— |
— |
— |
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
400A |
1 |
Box Lug |
31.1N-m (275in-lbs) 2x 350kcmil-1/0 |
CU-AL, Solid or Stranded |
130°C |
— |
— |
— |
|
400A |
3 |
Box Lug |
31.1N-m (275in-lbs) 2x 350kcmil-1/0 |
CU-AL, Solid or Stranded |
130°C |
— |
— |
— |
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
600A |
1 |
Box Lug |
42.4N-m (375in-lbs) 2x 500kcmil-4 |
CU-AL, Solid or Stranded |
130°C |
— |
— |
— |
|
600A |
3 |
Box Lug |
42.4N-m (375in-lbs) 2x 500kcmil-4 |
CU-AL, Solid or Stranded |
130°C |
— |
— |
— |
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|