Characteristics |
|
|
|
Main |
Range of product |
Harmony XALK |
|
Product or component type |
Complete control station |
|
Device short name |
XALK |
|
Product destination |
For XB5 Ø 22 mm control and signalling units |
|
Control station application |
Emergency stop function |
|
Colour of base of enclosure |
Light grey RAL 7035 |
|
Colour of cover |
Yellow RAL 1012 |
|
Material |
Polycarbonate |
|
Operator profile |
1 mushroom head pushbutton |
|
Operators description |
Red unmarked 1 NO + 1 NC |
|
Reset |
Turn to release |
|
Control station composition |
1 mushroom head Ø 40 mm pushbutton, red - 1 NO + 1 NC unmarked |
|
Contacts operation |
Slow-break |
|
Complementary |
Cable entry |
2 knock-outs for Pg 13 cable gland and ISO M20 <= 12 mm 1 knock-out for cable entry <= 14 mm |
|
Product weight |
0.194 kg |
|
Resistance to high pressure washer |
7000000 Pa at 55 °C, 0.1 m |
|
Positive opening |
With conforming to EN/IEC 60947-5-1 appendix K |
|
Operating travel |
4.3 mm total travel 2.6 mm NO changing electrical state 1.5 mm NC changing electrical state |
|
Operating force |
44 N NC + NO changing electrical state |
|
Mechanical durability |
300000 cycles |
|
Connections (Screw clamp terminals) |
>= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1 <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1 |
|
Tightening torque |
0.8...1.2 N.m conforming to EN/IEC 60947-1 |
|
Shape of screw head |
Slotted flat Ø 5.5 mm, Slotted flat Ø 4 mm, Cross pozidriv #1, Cross Philips #1 |
|
Contacts material |
Silver alloy (Ag/Ni) |
|
Short circuit protection |
10 A cartridge fuse, gG conforming to EN/IEC 60947-5-1 |
|
[Ith] conventional free air thermal current |
10 A conforming to EN/IEC 60947-5-1 |
|
[Ui] rated insulation voltage |
600 V, degree of pollution: 3 conforming to EN/IEC 60947-1 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-1 |
|
[Ie] rated operational current
(conforming to EN/IEC 60947-5-1) |
1.2 A at 600 V AC-15, A600 0.55 A at 125 V DC-13, Q600 0.27 A at 250 V DC-13, Q600 0.1 A at 600 V DC-13, Q600 6 A at 120 V AC-15, A600 3 A at 240 V AC-15, A600 |
|
Electrical durability
(load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C) |
1000000 cycles DC-13 at 0.5 A 24 V at 3600 cyc/h 1000000 cycles DC-13 at 0.2 A 110 V at 3600 cyc/h 1000000 cycles AC-15 at 4 A 24 V at 3600 cyc/h 1000000 cycles AC-15 at 3 A 120 V at 3600 cyc/h 1000000 cycles AC-15 at 2 A 230 V at 3600 cyc/h |
|
Electrical reliability (conforming to EN/IEC 60947-5-4) |
Λ < 10exp(-8) at 17 V and 5 mA Λ < 10exp(-6) at 5 V and 1 mA |
|
|
|
|
Environment |
Protective treatment |
TH |
|
Ambient air temperature for storage |
-40...70 °C |
|
Ambient air temperature for operation |
-25...70 °C |
|
Class of protection against electric shock |
Class II conforming to IEC 60536 |
|
IP degree of protection |
IP65 conforming to IEC 60529 |
|
NEMA degree of protection |
NEMA 4X, NEMA 13 |
|
IK degree of protection |
IK03 conforming to EN 50102 |
|
Standards |
EN/IEC 60204-1, EN/IEC 60947-1, EN/IEC 60947-5-1, EN/IEC 60947-5-4, EN/IEC 60947-5-5, EN/ISO 13850, JIS C 4520, UL 508, CSA C22.2 No 14 |
|
Product certifications |
CSA, UL listed |
|
Vibration resistance |
5 gn (f = 12...500 Hz) conforming to IEC 60068-2-6 |
|
Shock resistance |
50 gn (11 ms half sine wave acceleration) conforming to IEC 60068-2-27 30 gn (18 ms half sine wave acceleration) conforming to IEC 60068-2-27 |
|