USA, Canada |
REV 10/JAN/2018 |
|
|
|
Kühl® Series COMMERCIAL GRADE |
Room Air Conditioners |
Installs in a window or in-wall |
|
Tough enough for the most demanding applications |
Kühl is used in industrial and commercial applications where only the most rugged air conditioners can survive. |
|
Extensive testing |
Friedrich conducts rigorous performance tests in our own UL-certified lab to ensure customer satisfaction and safety. Run tests are performed for up to 120 continuous days under extreme temperature conditions. |
Air flow systems are tested for powerful and precise air distribution using state-of-the art Computational Fluid Dynamics (CFD). Sound levels are measured and optimized in our Friedrich sound lab to ensure ultra quiet performance. Premium air filters are tested for absorption capacities and efficiencies. |
The unit′s control software is tested for constant and reliable operation. Packaging exceeds ISTA (International Safe Transit Association) standards in order to withstand transportation hazards. |
Advanced design technology. Extensive product testing. It′s what you can expect from Friedrich. |
|
|
|
|
Energy Star |
Catalog Number |
Cooling Btu |
Heating Btu |
Volts |
Cooling Amps |
Cooling Watts |
Heating Amps |
Heating Watts |
EER |
CEER |
Estimated Yearly Energy Cost |
COP |
Moisture Removal- Pints/HR |
CFM |
Kühl® (Cool Only) |
|
SQ06N10C |
5800 |
— |
115 |
4.1 |
472 |
— |
— |
12.3 |
12.1 |
$43 |
— |
1.5 |
190 |
|
SQ08N10D |
8000 |
— |
115 |
6.1 |
656 |
— |
— |
12.2 |
12.0 |
$59 |
— |
1.9 |
200 |
|
SQ10N10C |
10000 |
— |
115 |
8.9 |
882 |
— |
— |
11.1 |
10.9 |
$79 |
— |
3.2 |
250 |
|
SS08N10C |
8000 |
— |
115 |
5.8 |
656 |
— |
— |
12.2 |
12.0 |
$59 |
— |
1.9 |
255 |
|
SS10N10C |
10000 |
— |
115 |
7.2 |
820 |
— |
— |
12.2 |
12.0 |
$74 |
— |
2.5 |
300 |
|
SS12N10C |
11900 |
— |
115 |
8.7 |
975 |
— |
— |
12.2 |
12.0 |
$88 |
— |
3.9 |
300 |
|
SS12N30C |
12000 11800 |
— |
230 208 |
4.5 4.9 |
984 967 |
— |
— |
12.2 12.2 |
12.0 12.0 |
$89 |
— |
3.6 |
300 |
|
SS14N10C |
13600 |
— |
115 |
10.4 |
1214 |
— |
— |
11.2 |
10.9 |
$109 |
— |
4.3 |
275 |
|
SS16N30C |
15500 15300 |
— |
230 208 |
6.5 7.1 |
1435 1417 |
— |
— |
10.8 10.8 |
10.7 10.7 |
$129 |
— |
5.0 |
330 |
|
SM14N10 |
13700 |
— |
115 |
9.9 |
1123 |
— |
— |
12.2 |
12.0 |
$101 |
— |
3.0 |
360 |
|
SM18N30C |
20000 20000 |
— |
230 208 |
9.3 10.2 |
2092 2041 |
— |
— |
10.3 10.3 |
10.3 10.3 |
$184 |
— |
6.0 |
425 |
|
SM21N30E |
20500 20500 |
— |
230 208 |
9.3 10.2 |
2092 2041 |
— |
— |
10.3 10.3 |
10.3 10.3 |
$188 |
— |
6.0 |
425 |
|
SL24N30C |
24000 24000 |
— |
230 208 |
10.2 11.1 |
2308 2308 |
— |
— |
10.4 10.4 |
10.3 10.3 |
$208 |
— |
7.0 |
640 |
|
SL28N30C |
28000 28000 |
— |
230 208 |
13.1 14.1 |
2800 2800 |
— |
— |
10.0 10.0 |
9.9 9.9 |
$252 |
— |
8.5 |
640 |
|
|
36000 35500 |
— |
230 208 |
17.5 19.2 |
4000 3944 |
— |
— |
9.0 9.0 |
9.0 9.0 |
$360 |
— |
12.0 |
725 |
Kühl®+ (Heat Pump) |
|
YS10N10C* |
10000 |
8800 |
115 |
7.9 |
917 |
9.0 |
978 |
10.9 |
10.8 |
$83 |
2.6 |
2.0 |
300 |
|
YS12N33C |
12000 12000 |
11300 11000 |
230 208 |
4.9 5.2 |
1101 1101 |
5.6 5.9 |
1257 1213 |
10.9 10.9 |
10.8 10.8 |
$99 |
2.6 2.7 |
3.0 |
375 |
|
YM18N34C |
17500 17200 |
15200 15200 |
230 208 |
7.1 7.6 |
1606 1578 |
7.3 8.0 |
1665 1665 |
10.9 10.9 |
10.8 10.8 |
$149 |
2.7 2.7 |
5.4 |
370 |
|
YL24N35D |
24000 24000 |
22000 22000 |
230 208 |
10.1 11.0 |
2330 2330 |
10.7 11.4 |
2391 2391 |
10.3 10.3 |
10.2 10.2 |
$210 |
2.6 2.6 |
7.0 |
600 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Kühl®+ (Electric Heat) |
|
|
8000 |
4000 |
115 |
6.1 |
656 |
11.2 |
1290 |
12.2 |
12.0 |
$61 |
— |
1.9 |
200 |
|
ES12N33B |
12000 12000 |
10700 8900 |
230 208 |
4.9 5.2 |
1062 1062 |
16.0 14.7 |
3500 2900 |
11.3 11.3 |
11.2 11.2 |
$96 |
— |
3.4 |
325 |
|
ES16N33C |
15500 15300 |
10700 8900 |
230 208 |
6.5 7.1 |
1435 1417 |
16.0 14.7 |
3500 2900 |
10.8 10.8 |
10.7 10.7 |
$129 |
— |
3.4 |
300 |
|
|
20000 20000 |
13000 10600 |
230 208 |
9.3 10.2 |
2041 2041 |
19.5 17.0 |
5500 4650 |
10.4 10.4 |
10.3 10.3 |
$225 |
— |
7.0 |
750 |
|
|
24000 24000 |
17300 14300 |
230 208 |
10.9 11.6 |
2308 2308 |
24.0 22.4 |
5500 4650 |
9.4 9.4 |
9.4 9.4 |
$225 |
— |
6.0 |
425 |
|
EL36N35B |
36000 35500 |
17300 14300 |
230 208 |
17.5 19.2 |
4000 3944 |
24.0 22.4 |
5500 4650 |
9.0 9.0 |
9.0 9.0 |
$360 |
— |
12.0 |
725 |
|
Catalog numbers in bold indicates active products in this group. Contact our sales office for the others. |
|
|
* YS10N10C heat pump operates on 115 volt and IS NOT equipped with supplemental heat. Will not provide heat at temperatures below 40°F (4.4°C). Friedrich room air conditioners are designed to operate in outdoor temperatures from 60°F (15.5°C) to 115°F (46.1°C). |
Kühl+ Heat Pump heating information indicates heat pump performance. Kühl+ Electric Heat heating information indicates electric heat strip performance. For Kühl+ Heat Pump electric heating performance refer to corresponding Kühl+ Electric Heat model. |
As an ENERGY STAR® partner, Friedrich Air Conditioning Co. has determined that the selected ENERGY STAR® models meet the ENERGY STAR® guidelines for energy efficiency. EER is the unit′s Energy Efficiency Ratio; CEER is the unit′s Combined Energy Efficiency Ratio. |
Your energy costs will depend on your utility rates and use. The estimated energy cost is based on an electricity cost of $.12 per kWh. For more information, visit External Weblink. |
Due to continuing research in new energy-saving technology, specifications are subject to change without notice. |
|
|
|
|
Comfort & Convenience |
• | Convenient control from your smartphone or computer via FriedrichLink® (required accessory sold separately) |
|
|
• | Up to 4 cooling and 4 fan-only speeds on select models† |
|
• | Automatic fan speed adjustment |
|
• | Auto-changeover from cool to heat; heat to cool to maintain set temperature (Kühl+ models except EQ08) |
|
|
• | Temperature readout can display set temperature and room temperature |
|
• | LCD panel auto dims if not in use |
|
• | LCD settings lockout option (ON/OFF) |
|
• | Premium remote control allows user to activate schedule, adjust temperature, adjust fan speed or select auto-fan; can also switch from cool to heat and heat to cool (Kühl + models) |
|
|
Sound Reduction Technology |
• | Steel inner wall and extra dense insulation materials block outdoor noise |
|
• | Vibration isolating design and components diminish traditional operating sound levels |
|
• | Precision engineering maximizes air flow while delivering ultra quiet operation |
|
|
Maintenance & Installation |
• | Check filter reminder and error code storage |
|
• | Same sleeve dimensions for 30+ years for easy replacement |
|
• | Slideout chassis for more permanent installation and easier access for maintenance |
|
• | Installs in a window or in-wall |
|
• | Includes heavy-duty window installation hardware (optional accessory on Kühl+ models) |
|
• | Rugged hardboard side panels or (heavy duty side curtains on SQ and EQ models) for a more permanent installation |
|
• | Power cord can run left or right |
|
• | Defrost control protects coil against freeze up |
|
• | Firm grip handles for easier chassis installation and removal |
|
|
Energy Management & Compliance |
• | Convenient control from your smartphone or computer via FriedrichLink® (optional accessory sold separately) |
|
• | 2 ready-to-go 7-day energy management programs |
|
• | Autofan mode saves money by conserving energy |
|
• | ENERGY STAR® qualified models, including heat pumps |
|
• | Environmentally-friendly R-410A refrigerant used in all models |
|
|
|
|
|
Safety & Security |
• | EntryGard™ anti-intrusion protection - secures chassis to the sleeve with a steel retaining wire to deter ′kick-in′ intrusion |
|
• | Power cord current leakage protected |
|
|
|
|
Health & IAQ |
• | Superior fresh air intake and stale air exhaust vent* |
|
• | Washable, antimicrobial air filter |
|
• | Premium carbon filter provides superior air filtration with ratings as high as MERV 6, while also adsorbing odors, and reducing ozone and VOCs when used in conjuction with standard filter |
|
• | Hinged door for easy filter access |
|
|
* Feature not available on SQ and EQ models. |
**Nut driver not required for Kühl SQ and EQ models. |
|
|
|
|
Cooling Sizing Guide |
|
Area to be conditioned in sq. ft. (m²) |
Approximate Cooling Btu (kW) Required |
|
Area to be conditioned in sq. ft. (m²) |
Approximate Cooling Btu (kW) Required |
|
100-150 ft² (9.3-13.9)m² |
5000 Btu (1.46 kW) |
|
550-700 ft² (51.0-65.0)m² |
14000 Btu (4.10 kW) |
|
150-250 ft² (13.9-23.2)m² |
6000 Btu (1.76 kW) |
|
700-1000 ft² (65.0-92.9)m² |
18000 Btu (5.27 kW) |
|
250-300 ft² (23.2-27.8)m² |
7000 Btu (2.05 kW) |
|
1000-1200 ft² (92.9-111.4)m² |
21000 Btu (6.15 kW) |
|
300-350 ft² (27.8-32.5)m² |
8000 Btu (2.34 kW) |
|
1200-1400 ft² (111.4-130.0)m² |
23000 Btu (6.74 kW) |
|
350-400 ft² (32.5-37.1)m² |
9000 Btu (2.64 kW) |
|
1400-1500 ft² (130.0-139.3)m² |
24000 Btu (7.03 kW) |
|
400-450 ft² (37.1-41.8)m² |
10000 Btu (2.93 kW) |
|
1500-2000 ft² (139.3-185.8)m² |
30000 Btu (8.79 kW) |
|
450-550 ft² (41.8-51.0)m² |
12000 Btu (3.52 kW) |
|
2000-2500 ft² (185.8-232.2)m² |
34000 Btu (9.96 kW) |
|
Based on normal room insulation, average number of sun exposed windows and two person occupancy. |
|
1. If heavily shaded, reduce cooling Btus required by 10% |
2. If very sunny, increase cooling Btus required by 10% |
3. Add 500 Btus per person over 2 people |
4. Add 4000 Btus if the area is a kitchen |
|
Specifications and information are nominal and are subject to change without notice.